5.2 Error Diagnosis and Troubleshooting

— 5-5 —

Status when Alarm Occurred

At power ON

A

,

B

Cause

Remedy

A

An out-of-range parameter was previously

set or loaded.

Reset all parameters in range. Otherwise,

re-load correct parameters.

B

Circuit board (1PWB) defective

Replace Servopack.

3. A.10

Display and Outputs

Digital Operator Display

Alarm Name

Alarm Output

A.10

Overcurrent

Output transistor is OFF

(alarm state)

Status when Alarm Occurred

During Servomotor

operation

When servo ON (/S-ON)

signal turned ON

A

,

B

, C, D

C,

D

At power ON

C

Cause

Remedy

A

Wiring grounded between Servopack and

Servomotor.

Check and correct wiring.

B

Servomotor phase-U, -V, or -W grounded.

Replace Servomotor.

C

• Circuit board (1PWB) defective
• Power transistor defective

Replace Servopack.

D

Current feedback circuit, power transistor,

or circuit board defective.

Replace Servopack.

4. A.31

Display and Outputs

Digital Operator Display

Alarm Name

Alarm Output

A.31

Position error pulse overflow

(position control only)

Output transistor is OFF

(alarm state)