Input clr cn1-18, Input, Clr cn1-19 – Yaskawa Sigma Mini User Manual

Page 60

Advertising
background image

APPLICATIONS

2.2.2 Position References cont.

— 2-16 —

(2) The error counter clear (CLR) signal must be ON for at least 20 μs. Otherwise, it be-

comes invalid.

Allowable Voltage Level and Timing for Reference Pulse Input

Reference Pulse Form

Electrical Specifications

Remarks

Sign + pulse train input

(SIGN + PULS signal)
Maximum reference

frequency: 450 kpps

¨

reference

©

reference

The signs for each

reference pulse are as

follows:

¨

: High level

©

: Low level

90° different two-phase

pulse train

(phase A + phase B)
Maximum reference

frequency

x 1 multiplier:

450 kpps

x 2 multiplier:

400 kpps

x 4 multiplier:

200 kpps

Phase B is 90°

behind phase B

Phase A

Phase B

Phase B is 90°

forward from phase B

Parameter Cn-02 (bits 3,

4 and 5) is used to

switch the input pulse

multiplier mode.

CCW pulse + CW pulse
Maximum reference

frequency: 450 kpps

CCW pulse

CW pulse

¨

reference

©

reference

SIGN

PULS

Clearing the Error Counter

Use the following procedure to clear the contents of the error counter.

Input CLR CN1-18

Error Counter Clear Input

For Position

Control

Input

/

CLR CN1-19

Error Counter Clear Input

For Position

Control

Setting the CLR signal to high level will set the following conditions:

• Sets the error counter inside the Servopack to 0.

• Disables position loop control.

2

Positions

Servopack

Clear

Position loop

error counter