4.2 Settings for Common Basic Functions

4-27

4

Operation

(2) Related Parameters

∗ The setting unit is a percentage of the motor rated force.

Note: When using SEMI F47 function, set 1000 ms.

Parameter

Meaning

When Enabled

Classification

Pn008

n.††0†

A main circuit low voltage is not detected.
[Factory setting]

After restart

Setup

n.††1†

A main circuit low voltage is detected, and the host
controller limits the force.

n.††2†

A main circuit low voltage is detected, and the SER-
VOPACK independently limits the force using Pn424
and Pn425.

Force Limit at Main Circuit Voltage Drop

 

 

Classification

Pn424

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 100

1%

50

Immediately

Setup

Release Time for Force Limit at Main

Circuit Voltage Drop

 

 

Classification

Pn425

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 1000

1 ms

100

Immediately

Setup

Pn509

Instantaneous Power Cut Hold Time

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

20 to 1000

1 ms

20

Immediately

Setup

Speed

Position

Force

Speed

Position

Force

Speed

Position

Force