4.5 Setting Absolute Linear Scale

4-37

4

Operation

4.5.2 Origin Setting (Fn020)

This function sets the current position of linear scale as the origin when using a linear scale.

The following absolute linear scale can be used.

Environmental resistant absolute linear scale made by Mitutoyo Corporation

ABS ST780A series

Model: ABS ST78†A

(1) Checking before Operation

Confirm the following before executing the origin setting.

• Write Prohibited Setting (Fn010) is set to permit writing.
• Servo OFF state
• Polarity Detection (Fn080) has been executed.

(2) Operating Procedure

Step

Display after Operation

Key

Operation

1

Press the

Key to select the utility function main

menu. And then, press the

or

Key to select

Fn020.

2

Press the

Key.

The display will be switched to the execution display
of Fn020 (Origin Setting).

3

or

Press the

or

Key to select ORGSET5.

4

Press the

Key. Origin setting will start. During

execution of origin setting, "Scale Origin Set" will be
displayed blinking.
At completion of origin setting, "Scale Origin Set"
stops blinking, and "BB" in the status display field
will change to "DONE."

5

Turn the SERVOPACK power supply OFF and then
ON again to validate the setting.

B B

− F U N C T I O N −

F n 0 1 F : F B O p M o t I D

F n 0 2 0 : S

− O r i g S e t

F n 0 3 0 : S o f t R e s e t

F n 0 8 0 : P o l e D e t e c t

O R G S E T 1

B B

S c a l e O r i g i n S e t

O R G S E T 5

B B

S c a l e O r i g i n S e t

B B

S c a l O r i g i n S e t