5.2 Tuning-less Function

5-15

5

Adjustments

(4) Parameters Disabled by Tuning-less Function

When the tuning-less function is enabled in the factory settings, the setting of these parameters are not avail-

able: Pn100, Pn101, Pn102, Pn103, Pn104, Pn105, Pn106, Pn160, Pn139, and Pn408. These gain-related
parameters, however, may become effective depending on the executing conditions of the functions specified

in the following table. If EasyFFT is executed when the tuning-less function is enabled, the settings in Pn100,

Pn104, Pn101, Pn105, Pn102, Pn106, and Pn103, as well as the manual gain switch setting, will be enabled,
but the settings in Pn408.3, Pn160.0, and Pn139.0 will be not enabled

.

Note: {: Available

×

: Not available

Parameters Disabled by Tuning-less Function

Related Functions and Parameters

Item

Name

Pn Number

Force Control

Easy

FFT

Mechanical

Analysis

(Vertical Axis

Mode)

Gain

Speed Loop Gain
2nd Speed Loop Gain

Pn100
Pn104

{

{

{

Speed Loop Integral Time
Constant

Pn101

×

{

{

2nd Speed Loop Integral Time
Constant

Pn105

Position Loop Gain
2nd Position Loop Gain

Pn102
Pn106

×

{

{

Mass Ratio

Pn103

{

{

{

Advanced

Control

Friction Compensation Function
Selection

Pn408.3

×

×

×

Anti-resonance Control Related
Switch

Pn160.0

×

×

×

Gain

Switching

Gain Switching Selection Switch

Pn139.0

×

×

×