3.8 Noise Control and Measures for Harmonic Suppression

3-43

3

Wiring and Connection

Connect the noise filter ground wire directly to the ground plate.

Do not connect the noise filter ground wire to other ground wires.

If a noise filter is located inside a control panel, connect the noise filter ground wire and the ground

wires from other devices inside the control panel to the ground plate for the control panel first, then

ground these wires.

Ground plate

Ground plate

Shielded
ground wire

Noise
Filter

Noise
Filter

SERVOPACK SERVOPACK

SERVOPACK SERVOPACK

Wrong

Correct

Noise
Filter

Control Panel

Ground

SERVOPACK

SERVOPACK

Ground plate