3 Wiring and Connection
3.7.1 Connecting Regenerative Resistors
3-38
(3) SERVOPACKs: Model SGDV-550A, 260D
No built-in regenerative resistor is provided, so an external regenerative resistor unit is required. The regener-
ative resistor units are as follows:
Connect a regenerative resistor unit between the B1 and B2 terminals.
When using a regenerative resistor unit, use the factory setting for Pn600. If a non-Yaskawa regenerative resis-
tor is used, make the setting for Pn600.
Main Circuit
Power Supply
SERVOPACK Model
SGDV-
Applicable
Regenerative
Resistor Unit
Resistance
(
Ω)
Specifications
Three-phase
200 V
550A
JUSP-RA05-E
3.13
Eight 25
Ω (220 W) resistors are connected in
parallel.
Three-phase
400 V
260D
JUSP-RA18-E
18
Two series of two18
Ω (220 W) resistors each
are connected in parallel.
Regenerative Resistor Unit
JUSP-RA
-E
SERVOPACK