4 Operation

4.2.3 Overtravel

4-8

• A linear servomotor under force control cannot be decelerated to stop. The linear servomotor is stopped

with the dynamic braking (DB) or coasts to a stop according to the setting of Pn001.0. After the linear servo-

motor stops, the servomotor will enter a coast state.

• For details on stopping methods after the servo OFF command is received or an alarm occurs, refer to 4.2.8

Stopping Linear Servomotor after Receiving Servo OFF Command or Alarm Occurrence.

„

When Motor Stopping Method is Set to Decelerate to Stop

Emergency stop force can be set with Pn406.

• The setting unit is a percentage of the rated force.
• The factory setting is 800% so that the setting is large enough a value to operate the linear servomotor at

maximum force. The maximum value of emergency stop force that is actually available, however, is limited

to the maximum force of the linear servomotor.

Pn406

Emergency Stop Force

 

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 800

1%

800

Immediately

Setup

Speed

Position