Output wiring, Caution, If output relays or transistors in the – IDEC MicroSmart User Manual

Page 108: Is destined for europe

Advertising
background image

3: I

NSTALLATION

AND

W

IRING

3-14

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Output Wiring

Relay Output

Transistor Sink Output

Transistor Source Output

Caution

• If output relays or transistors in the

MicroSmart

CPU or output modules should fail, outputs may

remain on or off. For output signals which may cause heavy accidents, provide a monitor circuit
outside the

MicroSmart

.

• Connect a fuse to the output module, selecting a fuse appropriate for the load.
• Use proper wires for output wiring.

All-in-one type CPU modules:

UL1015 AWG22 or UL1007 AWG18

Slim type CPU and I/O modules:

UL1015 AWG22

• When equipment containing the

MicroSmart

is intended for use in European countries, insert an

IEC 60127-approved fuse to each output of every module for protection against overload or
short-circuit. This is required when equipment containing the

MicroSmart

is destined for Europe.

7

COM1

0
1
2
3
4
5
6
7

Ry.OUT

1

02

3
COM0

NC

456

L

L

Fuse

L

L

L

AC

Fuse

Fuse

DC

DC

Load

L

L

L

Fuse

+

AC

Fuse

Fuse

DC

DC

+

+

+

Connect a fuse appropriate

for the load.

Fuse

Fuse

COM(–)

+V

0
1
2
3
4
5
6
7

Tr.OUT

01

234567

Connect a fuse
appropriate for the load.

L

Fuse

L

L

+ –

L

L

L

L

Load

L

COM(+)

–V

0
1
2
3
4
5
6
7

Tr.OUT

01

234567

Connect a fuse
appropriate for the load.

L

Fuse

L

L

+

L

L

L

L

Load

L

Fuse