Btoa (bcd to ascii), Btoa (bcd to ascii) -7 – IDEC MicroSmart User Manual

Page 259

Advertising
background image

14: D

ATA

C

ONVERSION

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

14-7

BTOA (BCD to ASCII)

Applicable CPU Modules

Valid Operands

For the valid operand number range, see pages 6-1 and 6-2.

When T (timer) or C (counter) is used as S1 or S2, the timer/counter current value is read out.

The quantity of digits to convert can be 1 through 5. Make sure that the quantity of digits designated by S2 is within the
valid range. If the S2 data is out of the valid range, a user program execution error will result, turning on special internal
relay M8004 and the ERR LED.

Since the BTOA instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction
should be used as required.

Valid Data Types

FC4A-C10R2/C

FC4A-C16R2/C

FC4A-C24R2/C

FC4A-D20K3/S3

FC4A-D20RK1/RS1 & FC4A-D40K3/S3

X

X

X

X

X

Operand

Function

I

Q

M

R

T

C

D

Constant

Repeat

S1 (Source 1)

Binar y data to conver t

X

X

X

X

X

X

X

X

S2 (Source 2)

Quantity of digits to conver t

X

X

X

X

X

X

X

1-5

D1 (Destination 1)

Destination to store conversion results

X

W (word)

I (integer)

X

S1

→ D1, D1+1, D1+2, D1+3, D1+4

When input is on, the 16-bit binar y data designated by S1 is conver ted
into BCD, and conver ted into ASCII data. The data is read from the low-
est digit as many as the quantity of digits designated by S2. The result
is stored to the destination star ting with the operand designated by D1.

The quantity of digits to conver t can be 1 through 5.

BTOA(W)

S1

*****

S2

*****

D1

*****

When a bit operand such as I (input), Q (output), M (internal relay), or R (shift register) is
designated as the source, 16 points are used.

When a word operand such as T (timer), C (counter), or D (data register) is designated as the
source or destination, 1 point is used.