IDEC MicroSmart User Manual

Page 376

Advertising
background image

22: D

UAL

/ T

EACHING

T

IMER

I

NSTRUCTIONS

22-2

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Valid Operands

For the valid operand number range, see page 6-2.

Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.

Destination operand D2 (system work area) uses 2 data registers starting with the operand designated as D2. Data registers
D0 through D1298 and D2000 through D7998 can be designated as D2. The two data registers are used for a system work
area. Do not use these data registers for destinations of other advanced instructions, and do not change values of these data
registers using the Point Write function on

WindLDR

. If the data in these data registers are changed, the dual timer does not

operate correctly.

The dual timer instructions cannot be used in an interrupt program. If used, a user program execution error will result,
turning on special internal relay M8004 and the ERR LED on the CPU module.

Examples: DTML, DTIM, DTMH, DTMS

For the timer accuracy of timer instructions, see page 7-8.

Operand

Function

I

Q

M

R

T

C

D

Constant

S1 (Source 1)

ON duration

X

0-65535

S2 (Source 2)

OFF duration

X

0-65535

D1 (Destination 1)

Dual timer output

X

▲ X — —

D2 (Destination 2)

System work area

D0-D7998

Instruction

Increments

S1

ON duration

S2

OFF duration

DTML

1 sec

2

1 sec

× 2 = 2 sec

1

1 sec

× 1 = 1 sec

DTIM

100 ms

10

100 ms

× 10 = 1 sec

5

100 ms

× 5 = 0.5 sec

DTMH

10 ms

50

10 ms

× 50 = 500 ms

25

10 ms

× 25 = 250 ms

DTMS

1 ms

250

1 ms

× 250 = 250 ms

125

1 ms

× 125 = 125 ms

500 ms

250 ms

I0

D2

D100

While input I0 is on, four dual timer instructions turn on and off
the destination operands according to the on and off durations
designated by source operands S1 and S2.

S1

2

D1

M10

DTML

S2

1

D2

D200

S1
10

D1

M20

DTIM

S2

5

D2

D300

S1
50

D1

M30

DTMH

S2
25

D2

D400

S1

250

D1

M40

DTMS

S2

125

M10

ON

OFF

M20

ON

OFF

M30

ON

OFF

I0

ON

OFF

2 sec

M40

ON

OFF

1 sec

1 sec

0.5 sec

250 ms

125 ms