IDEC MicroSmart User Manual

Page 289

Advertising
background image

17: U

SER

C

OMMUNICATION

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

17-11

Conversion Type

The BCC calculation result can be converted or not according to the designated conversion type as described below:

Example: BCC calculation result is 0041h.

(1) Binary to ASCII conversion

(2) No conversion

BCC Digits (Bytes)

The quantity of digits (bytes) of the BCC code can be selected from 1 or 2.

Example:

Transmit Completion Output

Designate an output, Q0 through Q107, or an internal relay, M0 through M1277, as an operand for the transmit completion
output. Special internal relays cannot be used.

When the start input for a TXD instruction is turned on, preparation for transmission is initiated, followed by data trans-
mission. When a sequence of all transmission operation is complete, the designated output or internal relay is turned on.

Transmit Status

Designate a data register, D0 through D1298 or D2000 through D7998, as an operand to store the transmit status informa-
tion including a transmission status code and a user communication error code.

Transmit Status Code

If the transmit status code is other than shown above, an error of transmit instruction is suspected. See User Communica-
tion Error Code on page 17-27.

Transmit

Status Code

Status

Description

16

Preparing transmission

From turning on the star t input for a TXD instruction, until the transmit
data is stored in the internal transmit buffer

32

Transmitting data

From enabling data transmission by an END processing, until all data
transmission is completed

48

Data transmission complete

From completing all data transmission, until the END processing is
completed for the TXD instruction

64

Transmit instruction complete

All transmission operation is completed and the next transmission is
made possible

0041h

Binar y to ASCII conversion

“4”

(34h)

“1”

(31h)

2 digits

ASCII data

Note: On WindLDR, Modbus ASCII is
defaulted to binar y to ASCII conversion.

0041h

No conversion

NUL

(00h)

“A”

(41h)

2 digits

ASCII data

Note: On WindLDR, Modbus RTU is
defaulted to no conversion.

(1) BCC digits = 2

“4”

(34h)

“1”

(31h)

“4”

(34h)

“1”

(31h)

(2) BCC digits = 1

“4”

(34h)

“1”

(31h)

“1”

(31h)

Lower digit

ASCII data

Note: On WindLDR, Modbus ASCII and
Modbus RTU are defaulted to 2 digits.