IDEC MicroSmart User Manual

Page 294

Advertising
background image

17: U

SER

C

OMMUNICATION

I

NSTRUCTIONS

17-16

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

User Communication Receive Instruction Dialog Box in WindLDR

Selections and Operands in Receive Instruction Dialog Box

Receive Format

Receive format, designated by source operand S1, specifies data registers to store received data, data digits for storing
data, data conversion type, and repeat cycles. A start delimiter and an end delimiter can be included in the receive format to
discriminate valid incoming communication. When some characters in the received data are not needed, “skip” can be
used to ignore a specified number of characters. BCC code can also be appended to the receive format to verify the
received data. One RXD instruction can receive 200 bytes of data at the maximum.

S1 (Source 1)

Designating Data Register as S1

When a data register is designated as source operand S1, receive digits and conversion type must also be designated. The
received data is divided into a block of specified receive digits, converted in a specified conversion type, and stored to the
designated data register. Conversion types are available in ASCII to Binary, ASCII to BCD, and no conversion.

When repeat is designated, received data is divided, converted, and stored into data registers as many as the repeat cycles,
starting with the designated data register. Repeat cycles can be up to 99.

Type

TXD

Transmit instruction

RXD

Receive instruction

Port

Port 1

Receive user communication through por t 1 (RXD1)

Port 2

Receive user communication through por t 2 (RXD2)

S1

Source 1

Enter the receive format in this area.
The receive format can include a star t delimiter, data register to store incoming data, end
delimiter, BCC, and skip.

D1

Destination 1

Receive completion output can be an output or internal relay.

D2

Destination 2

Receive status register can be data register D0 through D1298 or D2000 through D7998.
The next data register stores the byte count of received data.

Receive

Format

Operand

Receive

Digits

(Bytes)

Conversion Type

Repeat

BCC Calculation

Calculation

Start

Position

Skip

Bytes

Data Register

D0-D1299
D2000-D7999

1-4
1-5
1-2

A: ASCII to Binar y
B: ASCII to BCD
–: No conversion

1-99

Start Delimiter

00h-7Fh (FFh)

No conversion

End Delimiter

00h-7Fh (FFh)

No conversion

BCC

1-2

A: Binar y to ASCII
–: No conversion

X: XOR
A: ADD
C: Add-2comp
M: Modbus ASCII
M: Modbus RTU

1-15

Skip

1-99