As-i – IDEC MicroSmart User Manual

Page 443

Advertising
background image

28: AS-I

NTERFACE

M

ASTER

C

OMMUNICATION

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

28-3

AS-Interface Power Supply

The AS-Interface bus uses a dedicated 30V DC power supply (AS-Interface power
supply), which is indicated with the AS-Interface mark. General-purpose power sup-
ply units cannot be used for the AS-Interface bus.

Recommended IDEC AS-Interface Power Supplies

Cables

The AS-Interface bus uses only one cable to transmit signals and power. Use one of the following cable types (the wire
does not have to be stranded).

• Standard yellow unshielded AS-Interface cable (with polarity)
• Ordinary two-wire flat cable

Applicable Cable Specifications

Note: When using single wires, the maximum cable length is 200 mm. See “Maximum Communication Distance” on page
28-1.

• Use a VLSV (very low safety voltage) to power the AS-Interface bus.

The normal output voltage of the AS-Interface power supply is 30V DC.

Input Voltage

Output Voltage

Output Wattage

Type No.

100 to 240V AC

30.5V DC

73W

PS2R-Q30ABL

145W

PS2R-F30ABL

Cable Type

Cable Size/Manufacturer

Cross-sectional View

AS-Interface
Standard Cable

Cable sheath color:

Yellow

Conductor cross section:

1.5 mm

2

LAPP’s Cables
Type No: 2170228 (sheath material EPDM)
Type No: 2170230 (sheath material TPE)

2-wire Flat Cable
or
Single Wires
(See Note)

Conductor cross section
Stranded wire:

0.5 to 1.0 mm

2

Solid wire:

0.75 to 1.5 mm

2

AWG:

20 to 16

AS-Interface Marks

Caution

AS-Interface Cable

Two-wire Flat Cable

AS-Inter face –

AS-Inter face +

(blue)

(brown)

AS-Inter face –

AS-Inter face +

(blue)

(brown)

Advertising