Modem mode status data register, Modem mode status data register -7 – IDEC MicroSmart User Manual

Page 433

Advertising
background image

27: M

ODEM

M

ODE

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

27-7

Modem Mode Status Data Register

When the modem mode is enabled, data register D8111 stores a modem mode status or error code.

D8111 Value

Status

Description

0

Not in the modem mode

Modem mode is not enabled.

10

Ready for connecting line

Star t internal relays except for disconnecting line can
be turned on.

20

Sending initialization string
(originate mode)

A star t internal relay is in operation in the first tr y or
subsequent retrial.

21

Sending ATZ (originate mode)

22

Dialing

23

Disconnecting line

24

Sending AT command

25

Sending initialization string (answer mode)

26

Sending ATZ (answer mode)

30

Waiting for resending initialization string
(originate mode)

The command star ted by a star t internal relay was not
completed and is waiting for retrial.

31

Waiting for resending ATZ (originate mode)

32

Waiting for re-dialing

33

Waiting for re-disconnecting line

34

Waiting for resending AT command

35

Waiting for resending initialization string
(answer mode)

36

Waiting for resending ATZ (answer mode)

40

Line connected

Telephone line is connected. Only M8053 (disconnect
line) can be turned on.

50

AT command completed successfully

Command star ted by M8054-M8056 is completed suc-
cessfully.

60

AT command program error

Invalid character is included in the initialization string,
dial number, or AT command string.
Correct the program to include 0Dh in the AT command.

61

Simultaneous star t of commands

Two or more star t internal relays are on.
Correct the user program so that only one star t internal
relay goes on at a time.

62

Invalid command in on-line mode

A star t IR other than M8053 (disconnect line) is turned
on while the telephone line is connected.
Correct the program so that only the disconnect com-
mand is sent while the line is connected.

63

AT command execution error

Command failed in the first and all retr y cycles.

Advertising