Introduction

Dual timer instructions generate ON/OFF pulses of required durations from a designated output, internal relay, or shift
register bit. Four dual timers are available and the ON/OFF duration can be selected from 1 ms up to 65535 sec.

Teaching timer instruction measures the ON duration of the start input for the teaching timer instruction and stores the
measured data to a designated data register, which can be used as a preset value for a timer instruction.

DTML (1-sec Dual Timer)

DTIM (100-ms Dual Timer)

DTMH (10-ms Dual Timer)

DTMS (1-ms Dual Timer)

Applicable CPU Modules

FC4A-C10R2/C

FC4A-C16R2/C

FC4A-C24R2/C

FC4A-D20K3/S3

FC4A-D20RK1/RS1 & FC4A-D40K3/S3

X

While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.

The time range is 0 through 65535 sec.

S1

*****

D1

*****

DTML

S2

*****

D2

*****

While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.

The time range is 0 through 6553.5 sec.

S1

*****

D1

*****

DTIM

S2

*****

D2

*****

While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.

The time range is 0 through 655.35 sec.

S1

*****

D1

*****

DTMH

S2

*****

D2

*****

While input is on, destination operand D1 repeats to turn on
and off for a duration designated by operands S1 and S2,
respectively.

The time range is 0 through 65.535 sec.

S1

*****

D1

*****

DTMS

S2

*****

D2

*****