IDEC MicroSmart User Manual

Page 339

Advertising
background image

20: P

ULSE

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

20-11

Timing Chart for Disable Pulse Counting

This program demonstrates a timing chart of the PWM2 instruction without pulse counting.

D1

M20

I1

PWM
2

S1

D100

D102 = 0 (disable pulse counting)

Output Pulse Q1

Pulse Width Ratio D101

PWR1

Star t Input I1

• When input I1 is turned on, PWM2 star ts to generate output pulses at the frequency designated by the value

stored in data register D100. The pulse width is determined by the value stored in data register D101. While the
output pulses are sent out from output Q1, internal relay M20 remains on.

• When input I1 is turned off, PWM2 stops generating output pulses immediately, then internal relay M20 turns off

and internal relay M21 turns on.

• If the pulse width ratio value in D101 is changed while generating output pulses, the change takes effect in the

next scan. When changing the pulse width ratio, make sure that the timing of the change is much slower than the
output pulse frequency, so that the pulse width ratio is changed successfully.

PWR2

PWR3

Pulse Output ON M20

Pulse Output Complete M21

PWR1

PWR2

Advertising