IDEC MicroSmart User Manual

Page 24

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

2-4

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Function Specifications (All-in-One Type CPU Module)

CPU Module Specifications

System Statuses at Stop, Reset, and Restart

CPU Module

FC4A-C10R2
FC4A-C10R2C

FC4A-C16R2
FC4A-C16R2C

FC4A-C24R2
FC4A-C24R2C

Program Capacity

4,800 bytes
(800 steps)

15,000 bytes
(2,500 steps)

27,000 bytes
(4,500 steps)

Expandable I/O Modules

4 modules

I/O Points

Input

6

9

14

Expansion:
64

Output

4

7

10

User Program Storage

EEPROM

RAM Backup

Backup Duration

Approx. 30 days (typical) at 25°C after backup batter y fully charged

Backup Data

Internal relay, shift register, counter, data register

Battery

Lithium secondar y batter y

Charging Time

Approx. 24 hours for charging from 0% to 90% of full charge at 25°C

Battery Life

Approx. 1000 cycles of discharging down to 10% and full charging

Replaceability

Not possible to replace batter y

Control System

Stored program system

Instruction Words

35 basic
38 advanced

35 basic
40 advanced

35 basic
48 advanced

Processing
Time

Basic instruction

1.65 ms (1000 steps) See page A-1.

END processing

0.64 ms (not including expansion I/O ser vice, clock function processing, data
link processing, and interrupt processing) See page A-2.

Internal Relay

256

1024

1024

Shift Register

64

128

128

Data Register

400

1300

1300

Counter
(adding, dual pulse reversible,
up/down selection reversible)

32

100

100

Timer
(1-sec, 100-ms, 10-ms, 1-ms)

32

100

100

Input Filter

3 to 15 ms (selectable in increments of 1 ms)

Catch Input
Interrupt Input

Four inputs (I2 through I5) can be designated as catch inputs or interrupt inputs
Minimum turn on pulse width: 40 µs maximum
Minimum turn off pulse width: 150 µs maximum

Self-diagnostic Function

Power failure, watchdog timer, data link connection, user program EEPROM sum
check, timer/counter preset value sum check, user program RAM sum check,
keep data, user program syntax, user program writing, CPU module, clock IC, I/O
bus initialize, user program execution

Start/Stop Method

Turning power on and off
Star t/stop command in WindLDR
Turning star t control special internal relay M8000 on and off
Turning designated stop or reset input off and on

Mode

Output

Internal Relay, Shift Register,

Counter, Data Register

Timer Current Value

Keep Type

Clear Type

Run

Operating

Operating

Operating

Operating

Stop (Stop input ON)

OFF

Unchanged

Unchanged

Unchanged

Reset (Reset input ON)

OFF

OFF/Reset to zero

OFF/Reset to zero

Reset to zero

Restar t

Unchanged

Unchanged

OFF/Reset to zero

Reset to preset

Advertising