S1+0 Operation Mode

The value stored in the data register designated by operand S1+0 determines the frequency range of the pulse output.

0: 10 to 1,000 Hz

1: 100 to 10,000 Hz

2: 1,000 to 20,000 Hz

3: 10 to 20,000 Hz (upgraded CPU only)

S1+1 Steady Pulse Frequency

When S1+0 is set to 0 through 2, the value stored in the data register designated by operand S1+1 specifies the frequency
of the steady pulse output in percent of the maximum of the frequency range selected by S1+0. When S1+0 is set to 0 (10
to 1,000 Hz) or 1 (100 to 10,000 Hz), valid values for operand S1+1 are 1 through 100, thus the steady pulse frequency can
be 10 to 1,000 Hz or 100 to 10,000 Hz, respectively. When S1+0 is set to 2 (1,000 to 20,000 Hz), valid values for operand
S1+1 are 1 through 20 and the S1+1 value multiplied by 5 determines the steady pulse frequency, thus the steady pulse fre-
quency can be 1,000 to 20,000 Hz.

When S1+0 is set to 3, the value stored in the data register designated by operand S1+1 determines the frequency of the
steady pulse output directly. Valid values are 10 through 20,000.

S1+2 Initial Pulse Frequency

When S1+0 is set to 0 through 2, the value stored in the data register designated by operand S1+2 specifies the frequency
of the initial pulse output in percent of the maximum of the frequency range selected by S1+0. When S1+0 is set to 0 (10
to 1,000 Hz) or 1 (100 to 10,000 Hz), valid values for operand S1+2 are 1 through 100, thus the initial pulse frequency can
be 10 to 1,000 Hz or 100 to 10,000 Hz, respectively. When S1+0 is set to 2 (1,000 to 20,000 Hz), valid values for operand
S1+2 are 1 through 20 and the S1+2 value multiplied by 5 determines the initial pulse frequency, thus the initial pulse fre-
quency can be 1,000 to 20,000 Hz.

When S1+0 is set to 3, the value stored in the data register designated by operand S1+2 determines the frequency of the
initial pulse output directly. Valid values are 10 through 20,000.

S1+4

Reversible control enable

0: Reversible control disabled
1: Reversible control (single-pulse output)
2: Reversible control (dual-pulse output)

R/W

S1+5

Control direction

0: For ward
1: Reverse

R/W

S1+6

Preset value (high word)

1 to 100,000,000 (05F5 E100h)

R/W

S1+7

Preset value (low word)

S1+8

Current value (high word)

1 to 100,000,000 (05F5 E100h)

R

S1+9

Current value (low word)

S1+10

Error status

0 to 10

R

Operation Mode

Steady Pulse Frequency (Hz)

0 or 1

Maximum frequency (Hz) selected by S1+0

× S1+1 value (%)

2

Maximum frequency (Hz) selected by S1+0

× S1+1 value (×5%)

3

Steady pulse frequency (Hz) selected by S1+1

Operation Mode

Initial Pulse Frequency (Hz)

0 or 1

Maximum frequency (Hz) selected by S1+0

× S1+2 value (%)

2

Maximum frequency (Hz) selected by S1+0

× S1+2 value (×5%)

3

Initial pulse frequency (Hz) selected by S1+1

Operand

Function

Description

R/W