2: M

ODULE

S

PECIFICATIONS

2-24

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

DC Input Module Specifications

Type No.

FC4A-N08B1

FC4A-N16B1

FC4A-N16B3

FC4A-N32B3

Input Points and Common Lines

8 points in 1
common line

16 points in 1
common line

16 points in 1
common line

32 points in 2
common lines

Terminal Arrangement

See Input Module Terminal Arrangement on pages 2-26 through 2-28.

Rated Input Voltage

24V DC sink/source input signal

Input Voltage Range

20.4 to 28.8V DC

Rated Input Current

7 mA/point (24V DC)

5 mA/point (24V DC)

Input Impedance

3.4 k

4.4 k

Turn ON Time (24V DC)

4 ms

Turn OFF Time (24V DC)

4 ms

Isolation

Between input terminals:

Not isolated

Internal circuit:

Photocoupler isolated

External Load for I/O Interconnection

Not needed

Signal Determination Method

Static

Effect of Improper Input Connection

Both sinking and sourcing input signals can be connected. If any input
exceeding the rated value is applied, permanent damage may be caused.

Cable Length

3m (9.84 ft.) in compliance with electromagnetic immunity

Connector on Mother Board

MC1.5/10-G-3.81BK (Phoenix Contact)

FL20A2MA (Oki Electric Cable)

Connector Insertion/Removal Durability

100 times minimum

Internal Current Draw

All Inputs ON

25 mA (5V DC)
0 mA (24V DC)

40 mA (5V DC)
0 mA (24V DC)

35 mA (5V DC)
0 mA (24V DC)

65 mA (5V DC)
0 mA (24V DC)

All Inputs OFF

5 mA (5V DC)
0 mA (24V DC)

5 mA (5V DC)
0 mA (24V DC)

5 mA (5V DC)
0 mA (24V DC)

10 mA (5V DC)
0 mA (24V DC)

Weight

85g

100g

65g

100g

Input Internal Circuit

Input Usage Limits

When using the FC4A-N16B1 at 55°C in the normal mounting direction, limit
the inputs which turn on simultaneously along line (1). At 45°C, all inputs
can be turned on simultaneously at 28.8V DC as indicated with line (2).

When using the FC4A-N16B3 or -N32B3 at 55°C, limit the inputs which turn
on simultaneously on each connector along line (3). At 30°C, all inputs can
be turned on simultaneously at 28.8V DC as indicated with line (4).

When using the FC4A-N08B1, all inputs can be turned on simultaneously at
55°C, input voltage 28.8V DC.

FC4A-N08B1 and FC4A-N16B1

FC4A-N16B3 and FC4A-N32B3

Input

Inter

nal Cir

cuit

COM

3.3 k

Input

Inter

nal Cir

cuit

COM

4.3 k

Input V

oltage (V DC)

28.8

0

100

Input Simultaneous ON Ratio (%)

26.4

(2) 45°C

(1) 55°C

70

0

Input V

oltage (V DC)

28.8

0

100

Input Simultaneous ON Ratio (%)

26.4

(4) 30°C

90

(3) 55°C

70

0

24.0

50

Input Operating Range

The input operating range of the Type 1
(IEC 61131-2) input module is shown
below:

FC4A-N16B3 and FC4A-N32B3

Transition

OFF Area

Input V

oltage (V DC)

28.8

15

5

0

1.2

8.4

Input Current (mA)

ON Area

Area

7.0

4.2

24

FC4A-N08B1 and FC4A-N16B1

Transition

OFF Area

Input V

oltage (V DC)

28.8

15

5

0

0.9

6.4

Input Current (mA)

ON Area

Area

5.3

3.2

24

Advertising