6: A

LLOCATION

N

UMBERS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

6-17

D8002 CPU Module Type Information

Information about the CPU module type is stored to D8002.

0: FC4A-C10R2 or FC4A-C10R2C
1: FC4A-C16R2 or FC4A-C16R2C
2: FC4A-D20K3 or FC4A-D20S3
3: FC4A-C24R2 or FC4A-C24R2C
4: FC4A-D40K3 or FC4A-D40S3
6: FC4A-D20RK1 or FC4A-D20RS1

D8003 Memory Cartridge Information

When an optional memory cartridge is installed on the CPU module cartridge connector, information about the user pro-
gram stored on the memory cartridge is stored to D8003.

0:

FC4A-C10R2 or FC4A-C10R2C

1:

FC4A-C16R2 or FC4A-C16R2C

2:

FC4A-D20K3 or FC4A-D20S3

3:

FC4A-C24R2 or FC4A-C24R2C

4:

FC4A-D40K3 or FC4A-D40S3

6:

FC4A-D20RK1 or FC4A-D20RS1

255: The memor y car tridge does not store any user program.

D8026 Communication Mode Information

Communication mode information of port 1 and port 2 is stored to D8026.

D8029 System Program Version

The PLC system program version number is stored to D8029. This value is indicated in the PLC status dialog box called
from the

WindLDR

menu bar. Select Online > Monitor, then select Online > PLC Status. See page 29-1.

D8030 Communication Adapter Information

Information about the communication adapter installed on the port 2 connector (except for all-in-one 10-I/O type CPU
module) is stored to D8030.

0: RS232C communication adapter is installed
1: RS485 communication adapter is installed or no communication adapter is installed

D8031 Optional Cartridge Information

Information about the optional cartridge installed on the CPU module is stored to D8031.

0: No optional car tridge is installed
1: Clock car tridge is installed
2: Memor y car tridge is installed
3: Clock car tridge and memor y car tridge are installed

D8037 Quantity of Expansion I/O Modules

The quantity of expansion I/O modules connected to the all-in-one 24-I/O type CPU module or any slim type CPU module
is stored to D8037.

Bit 15

0

2

0

1

0

0

Por t 2
00: Maintenance Protocol
01: User Protocol
10: Data Link
11: Modem Protocol

Por t 1
0:

Maintenance Protocol

1:

User Protocol

D8026