Intelligent Module Access Status Code

The data register designated as STATUS stores a status code to indicate the operating status and error of the intelligent
module access operation. When status code 1, 3, or 7 is stored, take a corrective measure as described in the table below:

STPA Execution during Program Download

When downloading a user program, the CPU module is automatically stopped as default. Depending on the timing of the
initiation of the download and the total time to execute all STPA Read and Write instructions, some of the STPA instruc-
tions may not be executed. If this is the case, manually stop the CPU module. After more than 1 second, initiate user pro-
gram download as shown in the chart below.

Status

Code

Status

Description

RUNA

STPA

0

Normal

Intelligent module access is normal.

X

X

1

Bus error

The intelligent module is not installed correctly.
Power down the MicroSmar t modules, and re-install the intelli-
gent module correctly.

X

X

3

Invalid module number

The designated module number is not found.
Confirm the intelligent module number and correct the program.

X

X

7

Excessive multiple usage

More than 64 STPA READ and STPA WRITE instructions are used.
Eliminate the excess instructions.

X

STPA instructions

CPU module

One cycle to execute all STPAs

Run

Power up

Stop

Initiate download

Automatic stop

Executed

Not executed

Actual star t

to download

STPA instructions

CPU module

One cycle to execute all STPAs

Run

Power up

Stop

Manual stop

Executed

Initiate download

More than 1 sec

Automatic Stop Sequence

Manual Stop Sequence