IDEC MicroSmart User Manual

Page 193

Advertising
background image

7: B

ASIC

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

7-9

Timer Accuracy, continued

Timer Counting Error

Every timer instruction operation is individually based on asynchronous 16-bit reference timers. Therefore, an error occurs
depending on the status of the asynchronous 16-bit timer when the timer instruction is executed.

Timeout Output Error

The output RAM status is set to the actual output when the END instruction is processed. So, an error occurs depending on
the timing when the timeout output turns on in a scan cycle. The timeout output error shown below does not include output
delay caused by the hardware.

Maximum and Minimum of Errors

Notes:

Advance error does not occur at the timer input and timeout output.
Tet + Tte = 1 scan time
Increment is 1 sec (TML), 100 ms (TIM), 10 ms (TMH), or 1 ms (TMS).
The maximum advance error is: Increment – 1 scan time
The maximum behind error is: 3 scan times

The timer input error and timeout output error shown above do not include the input response time (behind error)
and output response time (behind error) caused by hardware.

Power Failure Memory Protection

Timers TML, TIM, TMH, and TMS do not have power failure protection. A timer with this protection can be devised using
a counter instruction and special internal relay M8121 (1-sec clock), M8122 (100-ms clock), or M8123 (10-ms clock).

Error

TML

(1-sec timer)

TIM

(100-ms timer)

TMH

(10-ms timer)

TMS

(1-ms timer)

Maximum

Advance error

1000 ms

100 ms

10 ms

1 ms

Behind error

1 scan time

1 scan time

1 scan time

1 scan time

Error

Timer Input Error

Timer Counting

Error

Timeout Output

Error

Total Error

Minimum

Advance error

0 (Note)

0

0 (Note)

0

Behind error

Tet

0

Tte

0

Maximum

Advance error

0 (Note)

Increment

0 (Note)

Increment – (Tet + Tte)

Behind error

1 scan time + Tet

1 scan time

Tte

2 scan times + (Tet + Tte)

Program Processing

Timeout Output RAM

ON

OFF

Actual Output

ON

OFF

END

1 scan time

TIM

END

Tte

Timeout output error is equal to Tte (behind error) and can
be between 0 and one scan time.

0 < Tte < 1 scan time

Tte: Time from the timer instruction execution to the END
processing

Ladder Diagram

I1

I1

ON

OFF

C2

ON

OFF

Timing Chart

10 sec

(10-sec Timer)

CNT

C2

1000

M8123

Reset

Pulse

Instruction

Data

LODN
LOD
CNT

I1
M8123
C2
1000

Program List

Note: Designate counter C2 used in this program as a keep type counter. See page 5-4.