Movn (move not) – IDEC MicroSmart User Manual

Page 222

Advertising
background image

9: M

OVE

I

NSTRUCTIONS

9-4

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

MOVN (Move Not)

Applicable CPU Modules

Valid Operands

For the valid operand number range, see pages 6-1 and 6-2.

Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.

When T (timer) or C (counter) is used as S1, the timer/counter current value is read out. When T (timer) or C (counter) is
used as D1, the data is written in as a preset value which can be 0 through 65535.

Valid Data Types

Examples: MOVN

FC4A-C10R2/C

FC4A-C16R2/C

FC4A-C24R2/C

FC4A-D20K3/S3

FC4A-D20RK1/RS1 & FC4A-D40K3/S3

X

X

X

X

X

Operand

Function

I

Q

M

R

T

C

D

Constant

Repeat

S1 (Source 1)

First operand number to move

X

X

X

X

X

X

X

X

1-99

D1 (Destination 1)

First operand number to move to

X

▲ X

X

X

X

1-99

W (word)

I (integer)

X

X

S1 NOT

→ D1

When input is on, 16-bit data from operand designated by S1 is inver ted
bit by bit and moved to operand designated by D1.

REP

**

S1(R)

*****

D1(R)

*****

MOVN(*)

When a bit operand such as I (input), Q (output), M (internal relay), or R (shift register) is
designated as the source or destination, 16 points are used. When repeat is designated for a
bit operand, the quantity of operand bits increases in 16-point increments.

When a word operand such as T (timer), C (counter), or D (data register) is designated as the
source or destination, 1 point is used. When repeat is designated for a word operand, the
quantity of operand words increases in 1-point increments.

M10 NOT

→ M50

When input I0 is on, the 16 internal relays star ting with M10 designated
by source operand S1 are inver ted bit by bit and moved to 16 internal
relays star ting with M50 designated by destination operand D1.

M10 through M17, M20 through M27 NOT

M50 through M57, M60 through M67

The ON/OFF statuses of the 16 internal relays M10
through M17 and M20 through M27 are inver ted
and moved to 16 internal relays M50 through M57
and M60 through M67. M50 is the LSB (least signif-
icant bit), and M67 is the MSB (most significant bit).

Before inversion

0

1

0

0

1

0

0

0

0

1

0

0

1

0

1

1

MSB

LSB

S1

After inversion

1

0

1

1

0

1

1

1

1

0

1

1

0

1

0

0

MSB

LSB

D1

I0

REP

S1 –
M10

D1 –
M50

MOVN(W)

(M27-M10):

(M67-M50):

810 NOT

→ D2

When input I1 is on, decimal constant 810 designated by source operand
S1 is conver ted into 16-bit binar y data, and the ON/OFF statuses of the
16 bits are inver ted and moved to data register D2 designated by destina-
tion operand D1.

D1

D0

64725

D2

810

Before inversion (810):

0

0

1

0

0

0

0

1

0

1

1

0

0

0

1

0

MSB

LSB

S1

After inversion (64725):

1

1

0

1

1

1

1

0

1

0

0

1

1

1

0

1

MSB

LSB

D1

I1

REP

S1 –

810

D1 –

D2

MOVN(W)

D30 NOT

→ D20

When input I2 is on, the data in data register
D30 designated by S1 is inver ted bit by bit and
moved to data register D20 designated by D1.

64605

D20

930

D30

I2

REP

S1 –

D30

D1 –

D20

MOVN(W)