I/o c – IDEC MicroSmart User Manual

Page 396

Advertising
background image

24: A

NALOG

I/O C

ONTROL

24-10

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Ladder Refresh Type Analog Output Module Data Register Allocation (FC4A-K2C1)

Data Register

Number Offset

Data Size

(word)

Parameter

Channel

Default

R/W

+0 (Low Byte)

1

Analog output signal type

CH0

FFh

R/W

+0 (High Byte)

— Reser ved —

All channels

00h

+1

3

Analog output data configuration

CH0

0

R/W

+4

1

Analog output signal type

CH1

00FFh

R/W

+5

3

Analog output data configuration

0

R/W

+8

1

Analog output data

CH0

0

R/W

+9

1

CH1

0

R/W

+10

1

Analog output operating status

CH0

R

+11

1

CH1

R

+12

3

— Reser ved —

All channels

R

Advertising