As-i – IDEC MicroSmart User Manual

Page 447

Advertising
background image

28: AS-I

NTERFACE

M

ASTER

C

OMMUNICATION

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

28-7

Power Supply

Power Supply Wiring Diagram

A recommended power supply wiring diagram is shown below. Use a common power switch for both the CPU module
power supply and AS-Interface power supply to make sure that both power supplies are turned on and off at the same time.

Note: A failed slave can be replaced with a new slave with address 0 without turning off the power to the CPU module and
the AS-Inter face line. But, if power has been turned off before replacing the slaves, install a new slave with address 0 and
take one of the following steps, because the AS-Inter face master module has to be initialized to enable communication.

Disconnect the AS-Inter face cable connector and turn on both power supplies. Five seconds later, connect the AS-Inter face
cable connector.

Turn on the CPU module power supply first. Five seconds later, turn on the AS-Inter face power supply.

• When turning off the power to the CPU module, also turn off the AS-Interface power supply. If the

CPU module is powered down and up while the AS-Interface power remains on, AS-Interface com-
munication may stop due to a configuration error, resulting in a communication error.

• Turn on the AS-Interface power supply no later than the CPU module power supply, except when

slave address 0 exists on the network. The two power supplies may be turned off in any order.

• Immediately after power-up, the CPU module cannot access slave I/O data in the AS-Interface mas-

ter module. Make the user program so that slave I/O data are accessed after special internal relay
M1945 (Normal_Operation_Active) has turned on. See page 28-24.

Caution

AS-Interface Power Supply

30V DC

Slim Type CPU Module

FC4A-D40K3

AS-Inter face Master Module
FC4A-AS62M

Slave 1

Slave 2

AC Power

CPU Module Power Supply

24V DC

Power Switch

AS-Inter face Power Switch (Note)

AS-Inter face Cable Connector

VLSV (ver y low safety voltage)

Advertising