17: U

SER

C

OMMUNICATION

I

NSTRUCTIONS

17-4

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Connecting RS485 Equipment through RS485 Port 2

Upgraded slim type CPU modules can use the RS485 user communication function. Using the RS485 user communica-
tion, a maximum of 31 RS485 devices can be connected to the

MicroSmart

CPU module.

When using port 2 for RS485 communication on the slim type CPU module, mount the RS485 communication module
(FC4A-HPC3) next to the CPU module.

When using port 2 for RS485 communication on the slim type CPU module with the optional HMI module, install the
RS485 communication adapter (FC4A-PC3) to the port 2 connector on the HMI base module (FC4A-HPH1).

Connect RS485 device to the RS485 terminals A, B, and SG of port 2 on the

MicroSmart

CPU module using a shielded

twisted pair cable as shown below. The total length of the cable for the RS485 user communication can be extended up to
200 meters (656 feet).

RS485 User Communication System Setup

31 devices maximum

RS485 Device

RS485 Device

RS485 Device

Shielded twisted pair cable
200 meters (656 feet) maximum
Core wire 0.3 mm

2

Por t 2

RS485 Communication Adapter

FC4A-PC3

HMI Base Module

FC4A-HPH1

Por t 2

RS485 Communication Module

FC4A-HPC3

Advertising