IDEC MicroSmart User Manual

Page 230

Advertising
background image

10: D

ATA

C

OMPARISON

I

NSTRUCTIONS

10-2

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Applicable CPU Modules

Valid Operands

For the valid operand number range, see pages 6-1 and 6-2.

Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.

When T (timer) or C (counter) is used as S1 or S2, the timer/counter current value is read out.

Valid Data Types

Special Internal Relays M8150, M8151, and M8152 in CMP=

Slim type CPU modules FC4A-D20RK1, -D20RS1, -D40K3, and -D40S3 have three special internal relays to indicate the
comparison result of the CMP= instruction. Depending on the result, one of the three special internal relays turns on.

When more than one CMP= or ICMP>= instruction is used, M8150, M8151, or M8152 indicates the result of the instruc-
tion that was executed last.

Examples: CMP>=

The following examples are described using the CMP

≥ instruction. Data comparison operation for all other data compari-

son instructions is the same for the CMP

≥ instruction.

• Data Type: Word

• Data Type: Integer

FC4A-C10R2/C

FC4A-C16R2/C

FC4A-C24R2/C

FC4A-D20K3/S3

FC4A-D20RK1/RS1 & FC4A-D40K3/S3

X

X

X

X

X

Operand

Function

I

Q

M

R

T

C

D

Constant

Repeat

S1 (Source 1)

Data to compare

X

X

X

X

X

X

X

X

1-99

S2 (Source 2)

Data to compare

X

X

X

X

X

X

X

X

1-99

D1 (Destination 1)

Comparison output

X

▲ — — — —

1-99

W (word)

I (integer)

X

X

When a bit operand such as I (input), Q (output), M (internal relay), or R (shift register) is
designated as the source, 16 points are used. When repeat is designated for a bit operand, the
quantity of operand bits increases in 16-point increments.

When a word operand such as T (timer), C (counter), or D (data register) is designated as the
source, 1 point is used. When repeat is designated for a word operand, the quantity of oper-
and words increases in 1-point increments.

The destination uses only 1 point of output or internal relay. When repeat is designated for
the destination, outputs or internal relays as many as the repeat cycles are used.

When S1 > S2, M8150 (greater than) turns on.
When S1 = S2, M8151 (equal to) turns on.
When S1 < S2, M8152 (less than) turns on.

S2

Value

M8150 M8151 M8152

D1

Status

(1) S1 > S2

ON

OFF

OFF

OFF

(2) S1 = S2

OFF

ON

OFF

ON

(3) S1 < S2

OFF

OFF

ON

OFF

S2

S1

(2)

(1)

(3)

Small

Large

When repeat is designated, the comparison result of the last
repeat cycle turns on one of the three special internal relays.

I0

REP

S1 –

D10

D1 –

Q0

CMP>=(W)

S2 –

D20

56

D20

50

D20

Q0 turned off

Q0 turned on

S2

D1

42

D10

127

D10

S1

I1

REP

S1 –

D30

D1 –

Q1

CMP>=(I)

S2 –

D40

–3

D40

–3

D40

Q1 turned off

Q1 turned on

S2

D1

–4

D30

12

D30

S1