IDEC MicroSmart User Manual

Page 51

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

2-31

Relay Output Module Specifications

Note: When relay output modules are connected to the all-in-one 24-I/O type CPU module or any slim type CPU module, the
maximum number of relay outputs that can be turned on simultaneously, including the outputs on the CPU module, are
shown below.

Output Delay

Type No.

FC4A-R081

FC4A-R161

Output Points and Common Lines

8 NO contacts in 2 common lines

16 NO contacts in 2 common lines

Terminal Arrangement

See Relay Output Module Terminal Arrangement on page 2-32.

Maximum Load Current

2A per point

7A per common line

8A per common line

Minimum Switching Load

0.1 mA/0.1V DC (reference value)

Initial Contact Resistance

30 m

Ω maximum

Electrical Life

100,000 operations minimum (rated load 1,800 operations/hour)

Mechanical Life

20,000,000 operations minimum (no load 18,000 operations/hour)

Rated Load (resistive/inductive)

240V AC/2A, 30V DC/2A

Dielectric Strength

Between output and

or

terminals:

1,500V AC, 1 minute

Between output terminal and internal circuit: 1,500V AC, 1 minute
Between output terminals (COMs):

1,500V AC, 1 minute

Connector on Mother Board

MC1.5/11-G-3.81BK
(Phoenix Contact)

MC1.5/10-G-3.81BK
(Phoenix Contact)

Connector Insertion/Removal Durability

100 times minimum

100 times minimum

Internal Current Draw

All Outputs ON

30 mA (5V DC)
40 mA (24V DC)

45 mA (5V DC)
75 mA (24V DC)

All Outputs OFF

5 mA (5V DC)
0 mA (24V DC)

5 mA (5V DC)
0 mA (24V DC)

Weight

110g

145g

Contact Protection Circuit for Relay Output

See page 3-15.

CPU Module Type

All-in-One 24-I/O CPU Module

Slim Type CPU Module

Maximum Relay Outputs Turning On Simultaneously

33

54

Command

Output Relay Status

OFF delay:

10 ms maximum

Chatter:

6 ms maximum

ON delay:

6 ms maximum

ON

OFF

ON

OFF