Programming WindLDR

The Communication page in the Function Area Settings must be programmed to enable the modem communication for
port 2. If required, communication parameters of the CPU module port 2 can also be changed.

Since these settings relate to the user program, the user program must be downloaded to the

MicroSmart

after changing

any of these settings.

1. From the

WindLDR

menu bar, select Configure > Function Area Settings. The Function Area Setting dialog box

appears.

2. Click the Communication tab, and select Modem Protocol in the Port 2 pull-down list.

3. Click the Configure button. The Communication Parameters dialog box appears. Change settings, if required.

The default communication parameters shown below are recommended.

4. Click the OK button.

Baud rate

9600 bps

Only when the modem connected on the communication line uses differ-
ent communication parameters than the default values of the

MicroSmart

,

set the matching communication parameters. Since the total of modem
communication parameters is 10 bits, set the value to a total of 10 bits.

Star t bit

1

Data bits

7

Parity

Even

Stop bit

1

Total

10 bits

Baud Rate (bps)

1200, 2400, 4800, 9600, 19200

Data Bits

7 or 8

Parity

None, Odd, Even

Stop Bits

1 or 2

Receive Timeout (ms)

10 to 2540 (10-ms increments)
(Receive timeout is disabled when 2550
is selected.)

Device Number

0 to 31