Timing Chart for Enable Pulse Counting

This program demonstrates a timing chart of the PWM1 instruction when pulse counting is enabled.

D1

M50

I0

PWM
1

S1

D200

D202 = 1 (enable pulse counting)

• When input I0 is turned on, PWM1 star ts to generate output pulses at the frequency designated by the value

stored in data register D200. The pulse width is determined by the value stored in data register D201. While the
output pulses are sent out from output Q0, internal relay M50 remains on.

• When the quantity of generated output pulses reaches the preset value designated by data registers D203 and

D204, PWM1 stops generating output pulses. Then internal relay M50 turns off, and internal relay M51 turns on.

• If the pulse width ratio value in D201 is changed while generating output pulses, the change takes effect in the

next scan. When changing the pulse width ratio, make sure that the timing of the change is much slower than the
output pulse frequency, so that the pulse width ratio is changed successfully.

• If input I0 is turned off before reaching the preset value, PWM1 stops generating output pulses immediately, then

internal relay M50 turns off and internal relay M51 turns on.

Output Pulse Q0

Pulse Width Ratio D201

PV1

PWR1

Star t Input I0

PWR2

PWR3

Preset Value D203·D204

PV1

PV2

PV3

Pulse Output ON M50

Pulse Output Complete M51

PV2

PWR1

PWR2