IDEC MicroSmart User Manual

Page 347

Advertising
background image

20: P

ULSE

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

20-19

Timing Chart for Reversible Control with Single Pulse Output

This program demonstrates a timing chart of the RAMP instruction when reversible control is enabled with single pulse
output.

D1

M50

I0

RAMP

S1

D200

D204 = 1 (reversible control with single pulse output)

• When input I0 is turned on, RAMP generates output pulses star ting at the initial frequency designated by the value

stored in data register D202. While the output pulses are sent out from output Q0, internal relay M50 remains on.

• Operation modes 0 through 2: The pulse frequency increases according to the frequency change rate value stored

in data register D203.

• Operation mode 3: The pulse frequency increases as long as the frequency change time stored in data register

D203.

• While the output pulse frequency is on the increase, internal relay M52 remains on.

• Depending on the control direction designated by the value stored in data register D205, control direction output

Q1 turns off or on while D205 stores 0 (for ward) or 1 (reverse), respectively.

• When the output pulse frequency reaches the steady pulse frequency designated by the value stored in data regis-

ter D201, internal relay M52 turns off. When the output pulse frequency star ts to decrease, internal relay M52
turns on again.

• When the quantity of generated output pulses reaches the preset value designated by data registers D206 and

D207, RAMP stops generating output pulses. Then internal relay M50 and M52 turn off, and internal relay M51
turns on.

• If the parameter values in D200 through D207 (except for D204) are changed while generating output pulses, the

change takes effect when star t input I0 is turned on for the next cycle.

• If the value stored in D204 is changed after star t input I0 has been turned on, the change can take effect only

after the CPU star ts again.

• If star t input I0 is turned off before reaching the preset value, RAMP stops generating output pulses immediately,

then internal relay M50 turns off and internal relay M51 turns on. When input I0 is turned on again, RAMP restar ts
to generate output pulses for another cycle, star ting at the initial pulse frequency.

Pulse Output Status M52

Output Pulse Q0

Star t Input I0

Control Direction Output Q1

Pulse Output Complete M51

Initial Pulse Frequency

Steady Pulse Frequency

Control Direction D205

0 (For ward)

1 (Reverse)

Pulse Output ON M50

Advertising