26: C

OMPUTER

L

INK

C

OMMUNICATION

26-4

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

RS232C/RS485 Converter FC2A-MD1

The RS232C/RS485 converter FC2A-MD1 is used to convert data signals between EIA RS232C and EIA RS485. This
converter makes it possible to connect a host device with RS232C interface to multiple

MicroSmart

CPU modules using

one cable.

Parts Description

Specifications

General Specifications

Serial Interface Specifications

Rated Power Voltage

Power terminals:
DC IN adapter jack:

24V DC ±20% (ripple 10% maximum)
9V DC, 350mA supplied from AC adapter

Current Draw

Power terminals: Approx. 40 mA at the rated voltage

Operating Temperature

0 to 60°C

Storage Temperature

–20 to +70°C

Operating Humidity

45 to 85% RH (no condensation)

Vibration Resistance

5 to 55 Hz, 60 m/sec

2

, 2 hours each in 3 axes

Shock Resistance

300 m/sec

2

, 3 shocks each in 3 axes

Dielectric Strength

1500V AC, 1 minute between live par ts and dead par ts

Insulation Resistance

10 M

Ω minimum between live parts and dead parts (500V DC megger)

Noise Resistance

Power terminals: ±1 kV, 1 µs (using noise simulator)

Weight

Approx. 550g

Standards in Compliance

EIA standard RS232C (D-sub 25-pin female connector)
EIA standard RS485 (screw terminals)

Communication Method

Half-duplex

Communication Configuration

1:N (N

≤ 32)

Communication Cable

Shielded twisted-pair cable

Communication Baud Rate

9600 bps (fixed)

Slave Stations

32 slave stations maximum (RS485 line)

Maximum Cable Length

RS232C: 15m (49.2 ft.)
RS485:

Total 200m (656 ft.)

RS232C
Signal Level

Conver ter

RS485
Signal Level

RS485 I/O

Termination Resistor

Transmit/Receive Data A
Transmit/Receive Data B

Signal Ground

Vcc (+24V)

GND

Power Indicator
Goes on when power is supplied

Transmit Data Indicator
Goes on when RS232C transmit data (pin #2) is on

Receive Data Indicator
Goes on when RS232C receive data (pin #3) is on

RS232C I/O
Connect to the RS232C por t on the computer

AC Adapter Jack

Frame Ground

Note: Connect 24V DC to POWER SUPPLY + and – terminals or connect an AC adapter with 9V DC, 350mA output to the AC
adapter jack.

Note: The FC2A-MD1 contains a 220

Ω termination resistor on the RS485 line, eliminating the need for an external termi-

nation resistor. To use the internal termination resistor, connect terminal T to terminal B. When the termination resistor is
not needed, disconnect terminal T from terminal B.

1

T

2

A

3

B

4

SG

5

FG

6

+

7

SD

RD

POWER

DC IN

RS485

SERIAL PORT

POWER SUPPLY
24V DC

RS232C

SERIAL POR

T

RS232C/RS485
CONVERTER

Type FC2A-MD1