Ibmv (indirect bit move) – IDEC MicroSmart User Manual

Page 226

Advertising
background image

9: M

OVE

I

NSTRUCTIONS

9-8

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

IBMV (Indirect Bit Move)

Applicable CPU Modules

Valid Operands

For the valid operand number range, see pages 6-1 and 6-2.

Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.

When T (timer) or C (counter) is used as S2 or D2, the timer/counter current value is read out.

Make sure that the last source data determined by S1+S2 and the last destination data determined by D1+D2 are within the
valid operand range. If the derived source or destination operand is out of the valid operand range, a user program execu-
tion error will result, turning on special internal relay M8004 and ERR LED on the CPU module.

Either source operand S2 or destination operand D2 does not have to be designated. If S2 or D2 is not designated, the
source or destination operand is determined by S1 or D1 without offset.

Examples: IBMV

Source operand S1 and destination operand D1 determine the type of operand. Source operand S2 and destination operand
D2 are the offset values to determine the source and destination operands.

As a result, when input I0 is on, the ON/OFF status of internal relay M15 is moved to output Q44.

FC4A-C10R2/C

FC4A-C16R2/C

FC4A-C24R2/C

FC4A-D20K3/S3

FC4A-D20RK1/RS1 & FC4A-D40K3/S3

X

Operand

Function

I

Q

M

R

T

C

D

Constant

Repeat

S1 (Source 1)

Base address to move from

X

X

X

X

X

0 or 1

1-99

S2 (Source 2)

Offset for S1

X

X

X

X

X

X

X

0-65535

D1 (Destination 1)

Base address to move to

X

▲ X — — X

1-99

D2 (Destination 2)

Offset for D1

X

X

X

X

X

X

X

0-65535

S1 + S2

→ D1 + D2

When input is on, the values contained in operands des-
ignated by S1 and S2 are added to determine the source
of data. The 1-bit data so determined is moved to desti-
nation, which is determined by the sum of values con-
tained in operands designated by D1 and D2.

IBMV

S1(R)

*****

S2

*****

D1(R)

*****

D2

*****

REP

**

S1 –
M10

I0

IBMV

S2

D10

D1 –

Q30

SOTU

REP

D2
C5

M10

+ D10 → Q30 + C5

M27

M10

M17

M20

M15

5th from M10

Q47

Q30

Q37

Q40

12th from Q30

Q44

If the value of data register D10 designated by source operand
S2 is 5, the source data is determined by adding the offset to
internal relay M10 designated by source operand S1.

If the current value of counter C5 designated by destination oper-
and D2 is 12, the destination is determined by adding the offset
to output Q30 designated by destination operand D1.