IDEC MicroSmart User Manual

Page 66

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

2-46

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Analog Input Specifications (END Refresh Type)

Type No.

FC4A-L03A1 / FC4A-J2A1

FC4A-L03AP1

Analog Input Signal Type

Voltage Input

Current Input

Thermocouple

Resistance

Thermometer

Input Range

0 to 10V DC

4 to 20 mA DC

Type K
(0 to 1300°C)
Type J
(0 to 1200°C)
Type T
(0 to 400°C)

Pt 100
3-wire type
(–100 to 500°C)

Input Impedance

1 M

Ω minimum

250

1 M

Ω minimum

1 M

Ω minimum

Allowable Conductor Resistance
(per wire)

200

Ω maximum

Input Detection Current

1.0 mA maximum

AD
Conversion

Sample Duration Time

10 (20) ms (Note 1)

10 (20) ms
(Note 1)

20 ms

Sample Repetition Time

20 ms

20 ms

40 (20) ms
(Note 1)

Total Input System
Transfer Time (Note 2)

60 (105) ms + 1 scan time
(Note 1)

60 (200) ms
+ 1 scan time
(Note 1)

80 (200) ms
+ 1 scan time
(Note 1)

Type of Input

Single-ended
input

Differential input

Operating Mode

Self-scan

Conversion Method

∑∆ type ADC

Input Error

Maximum Error at 25°C

±0.2% of full scale

±0.2% of full scale
+ cold junction
compensation
error
(±4°C maximum)

±0.2% of full
scale

Temperature Coefficient

±0.006% of full scale/°C

Repeatability after
Stabilization Time

±0.5% of full scale

Non-lineality

±0.2% of full scale

Maximum Error

±1% of full scale

Data

Digital Resolution

4096 increments (12 bits)
13,000 increments maximum (14 bits) (Note 3)

Input Value of LSB

2.5 mV

4 µA

K:

0.100°C/0.180°F

(0.325°C)

J:

0.100°C/0.180°F

(0.300°C)

T:

0.100°C/0.180°F

(0.100°C)

(Note 3)

0.100°C/0.180°F

(0.150°C)

(Note 3)

Data Type in Application
Program

Default:

0 to 4095

Optional: –32768 to 32767 (selectable for each channel) (Note 4)

Monotonicity

Yes

Input Data Out of Range

Detectable (Note 5)

Advertising