Troubleshooting diagram 8 – IDEC MicroSmart User Manual

Page 495

Advertising
background image

29: T

ROUBLESHOOTING

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

29-15

Troubleshooting Diagram 8

Turn off the power to the master station, and
turn on the power after a few seconds.

Is the error code

0 at all stations?

Is the

communication cable

connected to the RS485

por t correctly?

Call IDEC for assistance.

NO

Make sure of correct wiring (see page 25-2).

END

Turn off M8006 using WindLDR.

Check error codes for the troubled
stations (see page 25-4).

For the master station, click the
Reset COMx button (see page
25-11) or tur
n on M8007 during
operation using WindLDR.

Are error codes

cleared to 0 at all

stations?

Clear the error codes at all stations using
WindLDR (see page 29-2).

Data link communication is impossible.

NO

YES

YES

YES

NO

M8006: Data link communication prohibit flag

M8007: Data link communication initialize flag

NO

YES

Is data link selected

for por t 2 correctly?

NO

YES

YES

NO

Is the PWR LED on?

See Troubleshooting Diagram 1,
“The PWR LED does not go on.”

Is M8006 on at

the master station?

Check por t 2 settings using
WindLDR (see pages 25-7 and
25-8).

Select data link for por t 2 correctly and down-
load the user program again (see pages 25-7
and 25-8).