Example: Two-phase High-speed Counter for Counting Input Pulses from Rotary Encoder

This example demonstrates a program for two-phase high-speed counter HSC1 to punch holes in a paper tape at regular
intervals.

Description of Operation

A rotary encoder is linked to the tape feed roller directly, and
the output pulses from the rotary encoder are counted by the
two-phase high-speed counter in the

MicroSmart

CPU module.

When the high-speed counter counts 2,700 pulses, the compar-
ison output is turned on. When the comparison output is turned
on, the high-speed counter continues another cycle of counting.
The comparison output remains on for 0.5 second to punch
holes in the tape, and is turned off before the high-speed
counter counts 2,700 pulses again.

Program Parameters

Note: This example does not use the phase Z signal (input I2).

Programming WindLDR

Group 1 (I0 - I2)

Two/Single-phase High-speed Counter

High-speed Counter Settings

Two-phase High-speed Counter

Enable Comparison

Yes

Comparison Output

Q1

Use HSC Reset Input (I2)

No

HSC Reset Value (D8046)

To cause current value over flow ever y 2700 pulses, store 62836 to D8046
(65535 – 2700 + 1 = 62836)

Timer Preset Value

0.5 sec (needed for punching) programmed in TIM instruction

Feed Roller

Rotary Encoder

Tape Punch

Rolled Tape