Analog potentiometers – IDEC MicroSmart User Manual

Page 150

Advertising
background image

5: S

PECIAL

F

UNCTIONS

5-30

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Analog Potentiometers

The all-in-one 10- and 16-I/O type CPU modules and every slim type CPU module have one analog potentiometer. Only
the 24-I/O type CPU module has two analog potentiometers. The values (0 through 255) set with analog potentiometers 1
and 2 are stored to data registers D8057 and D8058, respectively, and updated in every scan.

The analog potentiometer can be used to change the preset value for a timer or counter.

Special Data Registers for Analog Potentiometers

Example: Changing Counter Preset Value Using Analog Potentiometer

This example demonstrates a program to change a counter preset value using analog potentiometer 1.

CPU Module

Analog Potentiometer 1

Analog Potentiometer 2

FC4A-C24R2 and FC4A-C24R2C

D8057

D8058

Other CPU Modules

D8057

Analog Potentiometer 1

Analog Potentiometer 2

(24-I/O Type Only)

All-in-One Type CPU Module

Slim Type CPU Module

Analog Potentiometer 1

CNT

C0

D8057

I1

Reset

Pulse

I0

Analog potentiometer 1 value is stored to data register D8057, which is used as a preset
value for counter C0.

The preset value is changed between 0 and 255 using the potentiometer.