Sample Program: PULS1

This program demonstrates a user program of the PULS1 instruction to generate 1,000 pulses at a frequency of 3 kHz from
output Q0, followed by 3,000 pulses at a frequency of 5 kHz.

Operand Settings

Operand

Function

Description

Allocation No. (Value)

S1+0

Operation mode

Frequency range 100 to 10,000 Hz

D0 (1)

S1+1

Output pulse frequency

10,000 Hz

× 30% (50%) = 3,000 Hz (5,000 Hz)

D1 (30)

→ (50)

S1+2

Pulse counting

Enable pulse counting

D2 (1)

S1+3

Preset value (high word)

1,000 (3,000)

D3 (0)

S1+4

Preset value (low word)

D4 (1000)

→ (3000)

S1+5

Current value (high word)

0 to 3,000

D5

S1+6

Current value (low word)

D6

S1+7

Error status

D7

D1+0

Pulse output ON

0: Pulse output OFF
1: Pulse output ON

M100

D1+1

Pulse output complete

0: Pulse output not complete
1: Pulse output complete

M101

D1+2

Pulse output over flow

0: Over flow not occurred
1: Over flow occurred (PULS1 only)

M102

M8120

REP

S1 –

50

MOV(W)

D1 –

D1

M101

SOTU

M8120 is the initialize pulse special internal relay.

When the CPU star ts, five MOV(W) instructions store first-stage
parameters to data registers D0 through D4.

D0 (operation mode): 1 (100 to 10,000 Hz)

D1 (output pulse frequency): 30 (10,000 Hz

× 30% = 3,000 Hz)

D2 (pulse counting): 1 (enable pulse counting)

D3 (preset value high word): 0

D4 (preset value low word): 1,000

Pulse data update flag M1 is reset (pulse data not updated).

Pulse output complete flag M101 is turned off.

When M101 is turned on, three MOV (W) instructions store sec-
ond-stage parameters to data registers D1, D3, and D4.

D1 (output pulse frequency): 50 (10,000 Hz

× 50% = 5,000 Hz)

D3 (preset value high word): 0

D4 (preset value low word): 3,000

Pulse data update flag M1 is set (pulse data updated).

When star t input I0 is turned on, PULS1 star ts to generate
3,000Hz output pulses in the first stage.

Pulse output complete M101 is turned off.

I0

SOTU

M1

REP

S1 –

1

MOV(W)

D1 –

D0

REP

S1 –

30

MOV(W)

D1 –

D1

REP

S1 –

1

MOV(W)

D1 –

D2

REP

S1 –

0

MOV(W)

D1 –

D3

REP

S1 –

1000

MOV(W)

D1 –

D4

M1

S

M1

R

M101

R

REP

S1 –

0

MOV(W)

D1 –

D3

REP

S1 –

3000

MOV(W)

D1 –

D4

M101

R

M101

D1

M100

PULS
1

S1
D0