24: A

NALOG

I/O C

ONTROL

24-16

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Ladder Refresh Type

The operating status of each analog output channel is stored to a data register determined by the data register number
selected in the Configure Parameters dialog box of the ANST macro.

Status Code

Analog Output Operating Status (END refresh type)

0

Normal operation

1

(reser ved)

2

Initializing

3

Invalid parameter or analog output channel not available on the installed analog module

4

Hardware failure (external power supply failure)

Operating Status Bit

Analog Output Operating Status (Ladder refresh type)

Bit 0

0

Operating status bit

Normal operation

1

Initializing, changing configuration, hardware initialization error

Bit 1

0

Parameter bit

Parameter configuration normal

1

Parameter configuration error

Bit 2

0

External power supply bit

External power supply normal

1

External power supply error

Bit 3

0

Output data error bit

Output data normal

1

Output data range error

Bit 4 to Bit 15

0

Reser ved

Normal operation