27: M

ODEM

M

ODE

27-2

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Applicable Modems

Any Hayes compatible modem can be used. Modems with a communications rate of 9600 bps or more between modems
are recommended. Use modems of the same make and model at both ends of the communication line.

Special Internal Relays for Modem Mode

Special internal relays M8050-M8077 are allocated to the modem mode. M8050-M8056 are used to send an AT command
or disconnect the telephone line. M8060-M8066 and M8070-M8076 turn on to indicate the results of the command.
M8057, M8067, and M8077 are used to indicate the status of the modem mode.

All completion and failure internal relays are turned off when another start internal relay is turned on.

Start and Result Internal Relays

When one of start internal relays M8050-M8056 is turned on, a corresponding command is executed once. To repeat the
command, reset the start internal relay and turn the internal relay on again.

Completion or failure of a command is determined as described below:

Completion:

The command is transmitted repeatedly as many as the retr y cycles specified in data register D8109.
When the command is completed successfully, the completion IR is turned on and the command is not
executed for the remaining cycles.

Failure:

The command is transmitted repeatedly but failed in all trials as many as the retr y cycles specified in
data register D8109.

Status Internal Relays

Note: While M8077 (line connection) is off, the

MicroSmart

cannot send and receive maintenance communication and user

communication through por t 2. When M8077 is turned on, maintenance communication or user communication is enabled
depending on the value stored in data register D8103 (on-line mode protocol selection).

Mode

Command

Start IR

Completion IR

Failure IR

Data Register

Originate Mode

Initialization String

M8050

M8060

M8070

D8145-D8169

ATZ

M8051

M8061

M8071

Dialing

M8052

M8062

M8072

D8170-D8199

Disconnect Mode

Disconnect Line

M8053

M8063

M8073

AT General Command Mode

AT Command

M8054

M8064

M8074

D8130-D8144

Answer Mode

Initialization String

M8055

M8065

M8075

D8145-D8169

ATZ

M8056

M8066

M8076

Status IR

Status

Description

M8057

AT Command Execution

ON:

AT command is in execution (star t IR is on)

OFF: AT command is not in execution (completion or failure IR is on)

M8067

Operational State

ON:

Command mode

OFF: On-line mode

M8077

Line Connection

ON:

Telephone line connected (Note)

OFF: Telephone line disconnected