Catching Rising Edge of Input Pulse

Catching Falling Edge of Input Pulse

Note: When two or more pulses enter within one scan, subsequent pulses are ignored.

Example: Maintaining Catch Input

When a catch input is received, the catch input relay assigned to a catch input is turned on for only one scan. This example
demonstrates a program to maintain a catch input status for more than one scan.

Actual Input

ON

OFF

Catch Input Relay

ON

OFF

(M8154-M8157)

Note

END
Processed

1 scan time

(I2 to I5)

Actual Input

ON

OFF

Catch Input Relay

ON

OFF

(M8154-M8157)

Note

END
Processed

(I2 to I5)

1 scan time

M0

M8154

Input I2 is designated as a catch input using the Function Area Settings.

When input I2 is turned on, special internal relay M8154 is turned on, and M0 is maintained
in the self-holding circuit.

When NC input I1 is turned off, the self-holding circuit is unlatched, and M0 is turned off.

M0 is used as an input condition for the subsequent program instructions.

M0

I1