Troubleshooting diagram 10 – IDEC MicroSmart User Manual

Page 497

Advertising
background image

29: T

ROUBLESHOOTING

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

29-17

Troubleshooting Diagram 10

Did you make

sure of source 1 operand of the

TXD instruction?

Call IDEC for assistance.

NO

Are communication

parameters set correctly

using WindLDR?

NO

Are inputs to

more than 5 TXD instructions on

simultaneously?

YES

Correct the program to make sure that
inputs to more than 5 TXD instructions do
not go on simultaneously.

Data is not transmitted correctly
in the user communication mode.

Set the communication parameters to
match those of the remote terminal using
WindLDR (see page 17-5).

Make sure that the busy signal at the
remote terminal does not exceed 5 sec.

NO

NO

Is the data register

designated as transmit status

used repeatedly?

Correct the program to replace the duplicate
data register with a dif ferent data register.

Is duration of

the busy signal at the remote

terminal less than

5 sec?

YES

NO

YES

Make sure that the transmit data desig-
nated as source 1 operand is correct.

YES

YES

When the user communication still has a problem after completing the above procedure,
also perform the procedure of Diagram 9 described on the preceding page.