Error causes and actions – IDEC MicroSmart User Manual

Page 484

Advertising
background image

29: T

ROUBLESHOOTING

29-4

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

CPU Module Operating Status, Output, and ERR LED during Errors

*1: When a program RAM sum check error occurs, operation is stopped momentarily for reloading the user program. After

completing the reloading, operation resumes.

*2: Operation star ts to run and outputs are turned on or off according to the user program as default, but it is also possible

to stop operation and turn off outputs using the Function Area Settings on WindLDR. See page 5-3.

Error Causes and Actions

0001h: Power Failure

This error indicates when the power supply is lower than the specified voltage. This error is also recorded when the power
is turned off. Clear the error code using the HMI module or

WindLDR

on a computer.

0002h: Watchdog Timer Error

The watchdog timer monitors the time required for one program cycle (scan time). When the time exceeds approximately
293 msec, the watchdog timer indicates an error. Clear the error code using the HMI module or

WindLDR

on a computer. If

this error occurs frequently, the

MicroSmart

CPU module has to be replaced.

0004h: Data Link Connection Error

This error indicates that the Function Area Settings for data link communication are incorrect or the cable is not connected
correctly. Make sure that slave stations are set to station numbers 1 through 31 using

WindLDR

. No duplication of station

numbers is allowed. See page 25-7.

To correct this error, make corrections in the Function Area Settings and download the user program to each station, or
connect the cable correctly. Turn power off and on again for the slave station. Then take one of the following actions:

• Turn power off and on for the master station.

• Initialize data link communication for the master station using

WindLDR

on a computer. See page 25-11.

• Turn on special internal relay M8007 (data link communication initialize flag) at the master station. See page 25-6.

0008h: User Program EEPROM Sum Check Error

The user program stored in the

MicroSmart

CPU module EEPROM is broken. Download a correct user program to the

MicroSmart

, and clear the error code using the HMI module or

WindLDR

on a computer.

When a memory cartridge is installed on the CPU module, the user program in the memory cartridge is checked.

0010h: Timer/Counter Preset Value Sum Check Error

The execution data of timer/counter preset values is broken. The timer/counter preset values are initialized to the values of
the user program automatically. Note that changed preset values are cleared and that the original values are restored. Clear
the error code using the HMI module or

WindLDR

on a computer.

Error Items

Operating

Status

Output

ERR LED

Checked at

Power failure

Stop

OFF

OFF

Any time

Watchdog timer error

Stop

OFF

ON

Any time

Data link connection error

Stop

OFF

OFF

Initializing data link

User program EEPROM sum check error

Stop

OFF

ON

Star ting operation

TIM/CNT preset value sum check error

Maintained

Maintained

OFF

Star ting operation

User program RAM sum check error

Stop *1

OFF

ON

During operation

Keep data error

Maintained/

Stop *2

Maintained/

OFF *2

OFF

Turning power on

User program syntax error

Stop

OFF

ON

Downloading user program

User program writing error

Stop

OFF

ON

Downloading user program

CPU module error

Stop

OFF

ON

Turning power on

Clock IC error

Maintained

Maintained

ON

Any time

I/O bus initialize error

Stop

OFF

ON

Turning power on

User program execution error

Maintained

Maintained

ON

Executing user program