IDEC MicroSmart User Manual

Page 61

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

2-41

Relay Output Specifications (Mixed I/O Module)

Output Delay

Mixed I/O Module Terminal Arrangement and Wiring Diagrams

FC4A-M08BR1 (Mixed I/O Module) — Screw Terminal Type

Applicable Terminal Block:

FC4A-PMT11P (supplied with the mixed I/O module)

Type No.

FC4A-M08BR1

FC4A-M24BR2

Output Points and Common Lines

4 NO contacts in 1 common line

8 NO contacts in 2 common lines

Maximum Load Current

2A per point
7A per common line

Minimum Switching Load

0.1 mA/0.1V DC (reference value)

Initial Contact Resistance

30 m

Ω maximum

Electrical Life

100,000 operations minimum (rated load 1,800 operations/hour)

Mechanical Life

20,000,000 operations minimum (no load 18,000 operations/hour)

Rated Load (resistive/inductive)

240V AC/2A, 30V DC/2A

Dielectric Strength

Between output and

or

terminals:

1,500V AC, 1 minute

Between output terminal and internal circuit: 1,500V AC, 1 minute
Between output terminals (COMs):

1,500V AC, 1 minute

Contact Protection Circuit for Relay Output

See page 3-15.

Command

Output Relay Status

OFF delay:

10 ms maximum

Chatter:

6 ms maximum

ON delay:

6 ms maximum

ON

OFF

ON

OFF

L

3

COM1

0
1
2
3

0
1
2
3

DC.IN

Ry.OUT

1

02

3
COM0

NC

012

Ry.OUT

DC.IN

Terminal No.

I/O

0

I0

1

I1

2

I2

3

I3

COM0

COM0

NC

NC

0

Q0

1

Q1

2

Q2

3

Q3

COM1

COM1

Fuse

L

AC

Fuse

Fuse

DC

DC

Load

L

L

+

+

+

Sink Input Wiring

• COM0 and COM1 terminals are not connected together internally.

• For wiring precautions, see pages 3-13 and 3-14.

Fuse

Relay Output Wiring

24V DC

+ –

2-wire Sensor

PNP

+

Source Input Wiring

24V DC

+

2-wire Sensor

NPN