As-i – IDEC MicroSmart User Manual

Page 450

Advertising
background image

28: AS-I

NTERFACE

M

ASTER

C

OMMUNICATION

28-10

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Configuring a Slave

Next, you have to set the slave configuration in the AS-Interface master module, either by using pushbuttons PB1 and PB2
on the AS-Interface master module or

WindLDR

.

Configuration Using Pushbuttons PB1 and PB2

1. Check that PWR LED and CMO LED on the AS-Interface master module are on (normal protected mode).

2. Press pushbuttons PB1 and PB2 together for 3 seconds. CMO LED turns off and LMO LED turns on (protected

mode).

3. Press pushbutton PB2 for 3 seconds. CNF LED flashes (configuration mode).

4. About 5 seconds later, press pushbutton PB1 for 3 seconds. All I/O LEDs blink once to complete configuration.

5. Shut down the CPU module and AS-Interface master module, and power up again. Check that FLT LED is off, which

indicates that configuration is complete.

6. Use WindLDR to view slave information on the Configure AS-Inter face Master dialog box and check that all slaves

are recognized correctly.