Analog I/O Modules

Analog I/O modules are available in 3-I/O types, 2-, 4-, and 8-input types, and 1- and 2-output types. The input channel
can accept voltage and current signals, thermocouple and resistance thermometer signals, or thermistor signals. The output
channel generates voltage and current signals.

Analog I/O Module Type Numbers

Name

I/O Signal

I/O Points

Category

Type No.

Analog I/O Module

Voltage (0 to 10V DC)
Current (4 to 20mA)

2 inputs

END Refresh Type

FC4A-L03A1

Voltage (0 to 10V DC)
Current (4 to 20mA)

1 output

Thermocouple (K, J, T)
Resistance thermometer (Pt100)

2 inputs

FC4A-L03AP1

Voltage (0 to 10V DC)
Current (4 to 20mA)

1 output

Analog Input Module

Voltage (0 to 10V DC)
Current (4 to 20mA)

2 inputs

FC4A-J2A1

Voltage (0 to 10V DC)
Current (4 to 20mA)
Thermocouple (K, J, T)
Resistance thermometer
(Pt100, Pt1000, Ni100, Ni1000)

4 inputs

Ladder Refresh Type

FC4A-J4CN1

Voltage (0 to 10V DC)
Current (4 to 20mA)

8 inputs

FC4A-J8C1

Thermistor (NTC, PTC)

8 inputs

FC4A-J8AT1

Analog Output Module

Voltage (0 to 10V DC)
Current (4 to 20mA)

1 output

END Refresh Type

FC4A-K1A1

Voltage (–10 to +10V DC)
Current (4 to 20mA)

2 outputs

Ladder Refresh Type

FC4A-K2C1

END Refresh Type and Ladder Refresh Type

Depending on the internal circuit design for data refreshing, analog I/O modules are categorized into two types.

END Refresh Type

Each END refresh type analog I/O module is allocated 20 data registers to store analog I/O data and parameters for con-
trolling analog I/O operation. These data registers are updated at ever y end processing while the CPU module is running.
WindLDR has ANST macro to program the analog I/O modules.

The CPU module checks the analog I/O configuration only once at the end processing in the first scan. If you have
changed the parameter while the CPU is running, stop and restar t the CPU to enable the new parameter.

Ladder Refresh Type

Each ladder refresh type analog I/O module can be allocated any data registers to store analog I/O data and parameters
for controlling analog I/O operation. The data registers are programmed in the ANST macro. Analog I/O data are updated
at the ladder step following the ANST macro. Analog I/O parameters are updated when the ANST macro is executed, so
analog I/O parameters can be changed while the CPU is running.

Analog I/O Module Category

END Refresh Type

Ladder Refresh Type

While CPU
is running

Parameter Refreshing

At the end processing in the first scan

When executing ANST macro

Analog I/O Data
Refreshing

At the end processing

In the step after ANST macro
(always refreshed whether input to ANST is
on or off)

While CPU
is stopped

Analog Output Data
Refreshing

When M8025 (maintain outputs while CPU
stopped) is on, output data is refreshed.
When off, output is turned off.

Maintains output status when the CPU is
stopped. Output data can be changed using
STPA instruction while the CPU is stopped.
See page 24-21.

Data Register Allocation