Catch Input

The catch input function is used to receive short pulses from sensor outputs regardless of the scan time. Input pulses
shorter than one scan time can be received. Four inputs I2 through I5 can be designated to catch a rising or falling edge of
short input pulses, and the catch input statuses are stored to special internal relays M8154 through M8157, respectively.
The Function Area Settings dialog box is used to designate inputs I2 through I5 as a catch input.

Normal input signals to input terminals are read when the END instruction is executed at the end of a scan.

Since these settings relate to the user program, the user program must be downloaded to the

MicroSmart

after changing

any of these settings.

Catch Input Specifications

Note: Input filter settings have no effect on the catch inputs. For the input filter function, see page 5-24.

Catch Input Terminals and Special Internal Relays for Catch Inputs

Programming WindLDR

1. From the

WindLDR

menu bar, select Configure > Function Area Settings. The Function Area Settings dialog box

appears.

2. Select the Special Input tab.

3. Select Catch Input in the Groups 1 through 4 pull-down list boxes. The Catch Input dialog box appears.

4. Select Catch Input Rising Edge or Catch Input Falling Edge in the pull-down list.

Minimum Turn ON Pulse Width

40 µs

Minimum Turn OFF Pulse Width

150 µs

Group

Catch Input No.

Special Internal Relay for Catch Input

Group 1

I2

M8154

Group 2

I3

M8155

Group 3

I4

M8156

Group 4

I5

M8157

Catch Input Rising/Falling Edge Selection

Catch Input Rising Edge
Catch Input Falling Edge