Introduction

This chapter describes the data link communication function used to set up a distributed control system.

A data link communication system consists of one master station and a maximum of 31 slave stations, each station com-
prising a 16- or 24-I/O type

MicroSmart

CPU module or any slim type CPU module. When the data link communication is

enabled, the master station has 12 data registers assigned for each slave station, and each slave station has 12 data registers
for communication with the master station. Using these data registers, the master station can send and receive data of 6
data registers to and from each slave station. No particular program is required for sending or receiving data in the data
link communication system.

When data of inputs, outputs, internal relays, timers, counters, or shift registers are moved to data registers using the move
instructions in the user program, these data can also be exchanged between the master and slave stations.

The

OpenNet Controller, MICRO

3

,

MICRO

3

C

, and FA-3S series PLCs can also be connected to the data link communica-

tion system.

The all-in-one 10-I/O type

MicroSmart

CPU module does not have data link communication capabilities.

Data Link Specifications

Electric Specifications

Compliance with EIA-RS485

Baud Rate

19,200 or 38,400 bps

Synchronization

Star t-stop synchronization
Star t bit:

1

Data bits:

7

Parity:

Even

Stop bit:

1

Communication Cable

Shielded twisted pair cable, core wire 0.3 mm

2

Maximum Cable Length

200m (656 feet) total

Maximum Slave Stations

31 slave stations

Refresh Mode

Separate refresh

Transmit/Receive Data

0 through 6 words each for transmission and receiving per slave station

Special Internal Relay

M8005-M8007:

communication control and error

M8080-M8116:

communication completion for each slave station

M8117:

communication completion for all slave stations

Data Register

D900-D1271:

transmit/receive data

Special Data Register

D8069-D8099:

communication error code

Master Station

Slave Station 1

Slave Station 31