6: A

LLOCATION

N

UMBERS

6-2

« FC4A M

ICRO

S

MART

U

SER

’

S

M

ANUAL

»

Slim Type CPU Modules

Notes:
•

The least significant digit of input, output, internal relay, and special internal relay operand number is an octal number (0
through 7). Upper digits are decimal numbers.

•

The allocation numbers of expansion inputs and outputs star t with I30 and Q30, respectively.

•

Note that input and output allocation numbers are not continuous between the CPU module and expansion I/O modules.

•

A maximum of 7 expansion I/O modules can be mounted on all slim type CPU modules. The maximum I/O points depend
on the CPU module type as described below.

•

The 20-I/O type CPU module (FC4A-D20K3 and FC4A-D20S3) can add a maximum of 128 I/O points, and use a maximum
of 148 points of inputs and outputs in total.

•

The 20-I/O relay output type CPU module (FC4A-D20RK1 and FC4A-D20RS1) can add a maximum of 224 I/O points, and
use a maximum of 244 points of inputs and outputs in total.

•

The 40-I/O type CPU module (FC4A-D40K3 and FC4A-D40S3) can add a maximum of 224 I/O points, and use a maximum
of 264 points of inputs and outputs in total.

•

Four models of the slim type CPU modules (FC4A-D20RK1, FC4A-D20RS1, FC4A-D40K3, and FC4A-D40S3) with system
program ver. 201 and higher can use the AS-Inter face master module, and have additional internal relays and data regis-
ters for AS-Inter face communication. Use WindLDR ver. 4.20 or higher to program the AS-Inter face operands. For details
about AS-Inter face communication, see a separate user’s manual for the AS-Inter face master module.

•

When the AS-Inter face master module is not connected, these AS-Inter face operands can be used for basic and advanced
instructions like ordinar y internal relays and data registers. Note that these operands cannot be designated for keep or
clear operands in the Function Area Settings dialog box in

WindLDR

. In addition, the clear operand data command of the

maintenance communication protocol and the designated reset input do not work on these AS-Inter face operands. The sta-
tuses of these AS-Inter face operands are maintained at power-up or when a reset input is turned on, but are cleared when
a keep data error occurs.

Operand

FC4A-D20K3
FC4A-D20S3

FC4A-D20RK1
FC4A-D20RS1

FC4A-D40K3
FC4A-D40S3

Allocation No.

Points

Allocation No.

Points

Allocation No.

Points

Input (I)

I0 - I7
I10 - I13

12

I0 - I7
I10 - I13

12

I0 - I7
I10 - I17
I20 - I27

24

Expansion Input (I)

I30 - I187

128
(140 total)

I30 - I307

224
(236 total)

I30 - I307

224
(248 total)

Output (Q)

Q0 - Q7

8

Q0 - Q7

8

Q0 - Q7
Q10 - Q17

16

Expansion
Output (Q)

Q30 - Q187

128
(136 total)

Q30 - Q307

224
(232 total)

Q30 - Q307

224
(240 total)

Internal Relay (M)

M0 - M1277

1024

M0 - M1277

1024

M0 - M1277

1024

AS-Interface
Internal Relay (M)

—

—

M1300 - M1997

560

M1300 - M1997

560

Special Internal
Relay (M)

M8000 - M8157

128

M8000 - M8157

128

M8000 - M8157

128

Shift Register (R)

R0 - R127

128

R0 - R127

128

R0 - R127

128

Timer (T)

T0 - T99

100

T0 - T99

100

T0 - T99

100

Counter (C)

C0 - C99

100

C0 - C99

100

C0 - C99

100

Data Register (D)

D0 - D1299

1300

D0 - D1299

1300

D0 - D1299

1300

AS-Interface Data
Register (D)

—

—

D1700 - D1999

300

D1700 - D1999

300

Expansion Data
Register (D)

—

—

D2000 - D7999

6000

D2000 - D7999

6000

Special Data
Register (D)

D8000 - D8199

200

D8000 - D8199

200

D8000 - D8199

200