6: A

LLOCATION

N

UMBERS

6-2

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Slim Type CPU Modules

Notes:

The least significant digit of input, output, internal relay, and special internal relay operand number is an octal number (0
through 7). Upper digits are decimal numbers.

The allocation numbers of expansion inputs and outputs star t with I30 and Q30, respectively.

Note that input and output allocation numbers are not continuous between the CPU module and expansion I/O modules.

A maximum of 7 expansion I/O modules can be mounted on all slim type CPU modules. The maximum I/O points depend
on the CPU module type as described below.

The 20-I/O type CPU module (FC4A-D20K3 and FC4A-D20S3) can add a maximum of 128 I/O points, and use a maximum
of 148 points of inputs and outputs in total.

The 20-I/O relay output type CPU module (FC4A-D20RK1 and FC4A-D20RS1) can add a maximum of 224 I/O points, and
use a maximum of 244 points of inputs and outputs in total.

The 40-I/O type CPU module (FC4A-D40K3 and FC4A-D40S3) can add a maximum of 224 I/O points, and use a maximum
of 264 points of inputs and outputs in total.

Four models of the slim type CPU modules (FC4A-D20RK1, FC4A-D20RS1, FC4A-D40K3, and FC4A-D40S3) with system
program ver. 201 and higher can use the AS-Inter face master module, and have additional internal relays and data regis-
ters for AS-Inter face communication. Use WindLDR ver. 4.20 or higher to program the AS-Inter face operands. For details
about AS-Inter face communication, see a separate user’s manual for the AS-Inter face master module.

When the AS-Inter face master module is not connected, these AS-Inter face operands can be used for basic and advanced
instructions like ordinar y internal relays and data registers. Note that these operands cannot be designated for keep or
clear operands in the Function Area Settings dialog box in

WindLDR

. In addition, the clear operand data command of the

maintenance communication protocol and the designated reset input do not work on these AS-Inter face operands. The sta-
tuses of these AS-Inter face operands are maintained at power-up or when a reset input is turned on, but are cleared when
a keep data error occurs.

Operand

FC4A-D20K3
FC4A-D20S3

FC4A-D20RK1
FC4A-D20RS1

FC4A-D40K3
FC4A-D40S3

Allocation No.

Points

Allocation No.

Points

Allocation No.

Points

Input (I)

I0 - I7
I10 - I13

12

I0 - I7
I10 - I13

12

I0 - I7
I10 - I17
I20 - I27

24

Expansion Input (I)

I30 - I187

128
(140 total)

I30 - I307

224
(236 total)

I30 - I307

224
(248 total)

Output (Q)

Q0 - Q7

8

Q0 - Q7

8

Q0 - Q7
Q10 - Q17

16

Expansion
Output (Q)

Q30 - Q187

128
(136 total)

Q30 - Q307

224
(232 total)

Q30 - Q307

224
(240 total)

Internal Relay (M)

M0 - M1277

1024

M0 - M1277

1024

M0 - M1277

1024

AS-Interface
Internal Relay (M)

M1300 - M1997

560

M1300 - M1997

560

Special Internal
Relay (M)

M8000 - M8157

128

M8000 - M8157

128

M8000 - M8157

128

Shift Register (R)

R0 - R127

128

R0 - R127

128

R0 - R127

128

Timer (T)

T0 - T99

100

T0 - T99

100

T0 - T99

100

Counter (C)

C0 - C99

100

C0 - C99

100

C0 - C99

100

Data Register (D)

D0 - D1299

1300

D0 - D1299

1300

D0 - D1299

1300

AS-Interface Data
Register (D)

D1700 - D1999

300

D1700 - D1999

300

Expansion Data
Register (D)

D2000 - D7999

6000

D2000 - D7999

6000

Special Data
Register (D)

D8000 - D8199

200

D8000 - D8199

200

D8000 - D8199

200